User Tools

Site Tools


programs:filter_programs

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Next revision
Previous revision
programs:filter_programs [2023/03/06 05:57] – created marilisebester_gmail.comprograms:filter_programs [2023/03/08 06:23] (current) marilisebester_gmail.com
Line 2: Line 2:
  
 Please note that to create a filter program, the following must be created first: Please note that to create a filter program, the following must be created first:
-  * "Filter" Mainline +  * "Filter" Mainline - created under setup_mainlines 
-  * Valves for each of the backflush valves on the filter station +  * Valves for each of the backflush valves on the filter station - created under setup_manage valves 
-  * DP (Differential Pressure) sensor+  * DP (Differential Pressure) sensor - created under setup_all sensors 
 +Should you require help in creating these, please contact your Farmsync Technician
  
-There are two scenarios that will be explained below: +=====Creating a Filter Program===== 
-  - Creating a Filter Program where flushing is managed by an external flush controller  +{{ :programs:program_details1.png?nolink&400 |}} 
-    - In this case, Farmsync only sends a start end command +  * A: “Name” – Enter name for the Filter Program 
-  - Creating a Filter Program that issues all commands from Farmsync +  * B: “External Reference” – For Farmsync internal use only 
-    - In this case all the flush times are set on Farmsync+  * C: “Station” – Select the relevant station that the filter is connected to from the dropdown list
  
 +Press "Save" in order to set the rest of the settings for this program
  
 +{{ :programs:program_details2.png?nolink&400 |}}
 +  * A: “Enabled Automatic Start”
 +    * It is important to note that if this function is ticked, the Flush program will run permanently, meaning even when no Valve program is running
 +    * If this option is taken, DO NOT add the Filter Flush program to a Valve Program, as this will cause a clash
 +    * If you want the Filter Flush program to run ONLY when the valve program is running, then this function must NOT be ticked
 +  * B: “Stop Remote Flush program when flushing done” – under construction
 +  * C: “Total Program Run Time (minutes)” – Enter the max Runtime (min) for the flush program
 +  * D: “Flush Duration (seconds)” – Enter the time duration (sec) allowed for each filter to flush 
 +  * E: “Flush Time Duration (seconds)” – Enter the time allowed between filters to pass before the next filter flushes
 +  * F: “Minimum duration between flush operations (seconds)” – Enter the min time duration between flush cycles
 +  * G: “Min Pressure to enable pressure flush (Bar)” – Enter the min pressure difference between in & outlet of filter allowed before filter flushes
 +  * H: “Min Pressure to enable time flush (Bar)” – Enter the min pressure the system must supply for flushing to occur (refer to supplier filter specifications)
 +  * I: “Pressure Flush Delay (seconds)” – Enter the time (sec) allowed to pass for pressure difference to be higher than min before flush is enabled
 +  * J: “Flush Duration Delay (seconds)” – enter the duration of time that must past from when flushing is triggered before the flushing valves open (eg. allows time for Mainvalve to close)
 +  * K: “Flush on Start” – When enabled, filter will flush when program starts
 +  * L: “Flush on End” – When enabled, filter will flush when program stops
 +  * M: “Filter Start Delay (seconds)” – Duration of time allowed to pass after filter program has started before filter flushes
 +
 +See below example of flush program times explained:
 +{{ :programs:1flush_timing.png?nolink&600 |}}
 +{{ :programs:flush_timing.png?nolink&600 |}}
 +
 +{{ :programs:program_details3.png?nolink&400 |}}
 +  * A: “Flush Activated Sensor” – 
 +  * B: “Flush Active Port” – 
 +  * C: “Before Filter or Differential Pressure Sensor” – Select the relevant Pressure Sensor / DP Sensor from the dropdown list
 +  * D: “After Filter Pressure Sensor” – Select the relevant Pressure Sensor from the dropdown list (if DP Sensor was selected in C, then this sensor can be left to "Not Set"
 +  * E: “Remote Flush Program to Start when Flushing” – 
 +  * F: “Remote Pause / Resume program when flushing” – Select the relevant program that must be paused if the flushing sequence is initiated, this program will resume once the flushing program is completed
 +  * G: “Mainline Control Valve” – Select the relevant Mainline Control Valve from the dropdown list, should one be present
 +  * H: “Mainline Control Valve Close Delay” – Enter the duration of time allowed to pass from when filter flush is initiated before the Mainline Control Valve must close
 +  * I: “Master Filter Program” – Select the relevant Filter program from the dropdown list
 +  * J: “Auto Start from Master Filter Program” – Enable if current filter program must start the same time as the Master Filter Program
 +
 +=====Flush Valves=====
 +{{ :programs:flush_valves.png?nolink&400 |}}
 +
 +Choose from the dropdown lists below the relevant Flush Valves that were created for the Filter under “Setup_Manage Valves”; Provision has been made for 32 valves in total.
programs/filter_programs.1678082237.txt.gz · Last modified: 2023/03/06 05:57 by marilisebester_gmail.com

Donate Powered by PHP Valid HTML5 Valid CSS Driven by DokuWiki