programs:filter_programs
                Differences
This shows you the differences between two versions of the page.
| Next revision | Previous revision | ||
| programs:filter_programs [2023/03/06 05:57] – created marilisebester_gmail.com | programs:filter_programs [2023/03/08 06:23] (current) – marilisebester_gmail.com | ||
|---|---|---|---|
| Line 2: | Line 2: | ||
| Please note that to create a filter program, the following must be created first: | Please note that to create a filter program, the following must be created first: | ||
| - |   * " | + |   * " | 
| - | * Valves for each of the backflush valves on the filter station | + |   * Valves for each of the backflush valves on the filter station  | 
| - | * DP (Differential Pressure) sensor | + |   * DP (Differential Pressure) sensor  | 
| + | Should you require help in creating these, please contact your Farmsync Technician | ||
| - | There are two scenarios that will be explained below: | + | =====Creating a Filter Program===== | 
| - |   - Creating a Filter Program  | + | {{ : | 
| - | - In this case, Farmsync only sends a start & end command | + |    | 
| - |    | + |   * B: “External Reference” – For Farmsync  | 
| - | - In this case all the flush times are set on Farmsync | + |   * C: “Station” – Select  | 
| + | Press " | ||
| + | {{ : | ||
| + | * A: “Enabled Automatic Start” | ||
| + |     * It is important to note that if this function is ticked, the Flush program will run permanently, | ||
| + | * If this option is taken, DO NOT add the Filter Flush program to a Valve Program, as this will cause a clash | ||
| + | * If you want the Filter Flush program to run ONLY when the valve program is running, then this function must NOT be ticked | ||
| + | * B: “Stop Remote Flush program when flushing done” – under construction | ||
| + | * C: “Total Program Run Time (minutes)” – Enter the max Runtime (min) for the flush program | ||
| + | * D: “Flush Duration (seconds)” – Enter the time duration (sec) allowed for each filter to flush | ||
| + | * E: “Flush Time Duration (seconds)” – Enter the time allowed between filters to pass before the next filter flushes | ||
| + | * F: “Minimum duration between flush operations (seconds)” – Enter the min time duration between flush cycles | ||
| + | * G: “Min Pressure to enable pressure flush (Bar)” – Enter the min pressure difference between in & outlet of filter allowed before filter flushes | ||
| + | * H: “Min Pressure to enable time flush (Bar)” – Enter the min pressure the system must supply for flushing to occur (refer to supplier filter specifications) | ||
| + | * I: “Pressure Flush Delay (seconds)” – Enter the time (sec) allowed to pass for pressure difference to be higher than min before flush is enabled | ||
| + | * J: “Flush Duration Delay (seconds)” – enter the duration of time that must past from when flushing is triggered before the flushing valves open (eg. allows time for Mainvalve to close) | ||
| + | * K: “Flush on Start” – When enabled, filter will flush when program starts | ||
| + | * L: “Flush on End” – When enabled, filter will flush when program stops | ||
| + | * M: “Filter Start Delay (seconds)” – Duration of time allowed to pass after filter program has started before filter flushes | ||
| + | |||
| + | See below example of flush program times explained: | ||
| + | {{ : | ||
| + | {{ : | ||
| + | |||
| + | {{ : | ||
| + | * A: “Flush Activated Sensor” – | ||
| + | * B: “Flush Active Port” – | ||
| + | * C: “Before Filter or Differential Pressure Sensor” – Select the relevant Pressure Sensor / DP Sensor from the dropdown list | ||
| + | * D: “After Filter Pressure Sensor” – Select the relevant Pressure Sensor from the dropdown list (if DP Sensor was selected in C, then this sensor can be left to "Not Set" | ||
| + | * E: “Remote Flush Program to Start when Flushing” – | ||
| + | * F: “Remote Pause / Resume program when flushing” – Select the relevant program that must be paused if the flushing sequence is initiated, this program will resume once the flushing program is completed | ||
| + | * G: “Mainline Control Valve” – Select the relevant Mainline Control Valve from the dropdown list, should one be present | ||
| + | * H: “Mainline Control Valve Close Delay” – Enter the duration of time allowed to pass from when filter flush is initiated before the Mainline Control Valve must close | ||
| + | * I: “Master Filter Program” – Select the relevant Filter program from the dropdown list | ||
| + | * J: “Auto Start from Master Filter Program” – Enable if current filter program must start the same time as the Master Filter Program | ||
| + | |||
| + | =====Flush Valves===== | ||
| + | {{ : | ||
| + | |||
| + | Choose from the dropdown lists below the relevant Flush Valves that were created for the Filter under “Setup_Manage Valves”; Provision has been made for 32 valves in total. | ||
programs/filter_programs.1678082237.txt.gz · Last modified: 2023/03/06 05:57 by marilisebester_gmail.com