programs:filter_programs
This is an old revision of the document!
Filter Program
Please note that to create a filter program, the following must be created first:
- “Filter” Mainline
- Valves for each of the backflush valves on the filter station
- DP (Differential Pressure) sensor
There are two scenarios that will be explained below:
- Creating a Filter Program where flushing is managed by an external flush controller
- In this case, Farmsync only sends a start & end command
- Creating a Filter Program that issues all commands from Farmsync
- In this case all the flush times are set on Farmsync
Using an external flush controller
- A: “Name” – Enter a name for the Filter Program
- B: “External Reference” – For Farmsync internal use only
- C: “Station” – Select the relevant station that the filter is connected to from the dropdown list
- A: “Enabled Automatic Start”
- It is important to note that if this function is ticked, the Flush program will run permanently, meaning even when no Valve program is running
- If this option is taken, DO NOT add the Filter Flush program to a Valve Program, as this will cause a clash
- If you want the Filter Flush program to run ONLY when the valve program is running, then this function must NOT be ticked
- B: “Stop Remote Flush program when flushing done” – under construction
- C: “Total Program Run Time (minutes)” – Enter the max Runtime (min) for the flush program
- D: “Flush Duration (seconds)” – Enter the time duration (sec) allowed for each filter to flush
- E: “Flush Time Duration (seconds)” – Enter the time allowed between filters to pass before the next filter flushes
- F: “Minimum duration between flush operations (seconds)” – Enter the min time duration between flush cycles
- G: “Min Pressure to enable pressure flush (Bar)” – Enter the min pressure difference between in & outlet of filter allowed before filter flushes
- H: “Min Pressure to enable time flush (Bar)” – Enter the min pressure the system must supply for flushing to occur (refer to supplier filter specifications)
- I: “Pressure Flush Delay (seconds)” – Enter the time (sec) allowed to pass for pressure difference to be higher than min before flush is enabled
- J: “Flush Duration Delay (seconds)” – enter the duration of time that must past from when flushing is triggered before the flushing valves open (eg. allows time for Mainvalve to close)
- K: “Flush on Start” – When enabled, filter will flush when program starts
- L: “Flush on End” – When enabled, filter will flush when program stops
- M: “Filter Start Delay (seconds)” – Duration of time allowed to pass after filter program has started before filter flushes
See below example of flush program times explained:
- A: “Flush Activated Sensor” –
- B: “Flush Active Port” –
- C: “Before Filter or Differential Pressure Sensor” – Select the relevant Pressure Sensor / DP Sensor from the dropdown list
- D: “After Filter Pressure Sensor” – Select the relevant Pressure Sensor from the dropdown list (if DP Sensor was selected in C, then this sensor can be left to “Not Set”
- E: “Remote Flush Program to Start when Flushing” –
- F: “Remote Pause / Resume program when flushing” – Select the relevant program that must be paused if the flushing sequence is initiated, this program will resume once the flushing program is completed
- G: “Mainline Control Valve” – Select the relevant Mainline Control Valve from the dropdown list, should one be present
- H: “Mainline Control Valve Close Delay” – Enter the duration of time allowed to pass from when filter flush is initiated before the Mainline Control Valve must close
- I: “Master Filter Program” – Select the relevant Filter program from the dropdown list
- J: “Auto Start from Master Filter Program” – Enable if current filter program must start the same time as the Master Filter Program
programs/filter_programs.1678255881.txt.gz · Last modified: 2023/03/08 06:11 by marilisebester_gmail.com